Generators are mainly applied for telecoms stations in telecoms industry. Usually, generator sets 800KW are needed for provincial station, and generator sets 300KW to 400KW are needed for municipal station, as standby power. For town or county station, 120KW and below are needed, usually as prime power.
1.Automatic functions
Auto start and auto loading
After receiving the start directive, the machine will start up automatically, with 99% success ratio. A start circle containers three start attempts. The interval between two start attempts is 10 to 15 seconds.
After successful start up, when the oil pressure reaches set value, the machine will load automatically. The load time is usually 10 seconds.
After three times of startup failure, the machine will give alarm reporting, and give start directive to the other standby generator set, if there is any.
Auto stop
When receiving the stop directive, the machine will stop automatically. There are two types: normal stop and emergency stop. The normal stop is to stop the power (and then break the air switch or switch ATS to the main). The emergency stop is to cut the power and fuel supply immediately.
Auto protection
The machines have protection against low oil pressure, over voltage, over speed, overload, short circuit and lack of phase. For water-cooled machines, also high water temperature protection is provided and high cylinder temperature protection for air-cooled machines.
2.Remote Control
The machine provides remote control system, monitoring the real time operation parameters and state. When abnormality or serious faults occur, the machine will give alarms. Standard communication protocols can be provided.
3.Paralleling operation
It can be realized through ATS auto switch between the main and generator or between two generators . Also, two or more same model generators can be paralleled to ensure bigger capability. The stable state speed regulation ratio is between 2% and 5%. The stable state voltage regulation is within 5%.
4.Working conditions
Altitude height 3000 meters and below. Temperature lower limit -15°C, upper limit 40°C
5.Stable performance & high reliability
Average failure interval not less than 2000 hours
6.Convenient refueling and protection
Lockable exterior refueling system Large fuel tank, supporting 12 hours to 24 hours operation.